OMRON CRS1-RPT01 Automation Systems
last update: December 19, 2013
Repeater Units can make CompoNet Networks easier to wire, and extend cable length.
When Repeater Units are connected in series from the Master Unit, up to two extra segment layers can be created (i.e., up to 2 Repeater Units are allowed between a Slave Unit and the Master Unit).
• Expand the network to up to 1,500 m using two segment layers of Repeater Units (baud rate: 93.75 kbps)
• Avoid total system breakdown caused by errors in lower-level Units.
• Repeater Units allow a different cable types to be used in the same network.
• Implement various network layouts by branching lines or extending the trunk line.
• Display a network configuration list or identify error locations by using the setting and monitoring software for CompoNet.
• Monitor the power supply for the entire network with communications power supply monitoring function.
last update: December 19, 2013
If you have just landed here, this product OMRON CRS1-RPT01 Automation Systems,Automation Systems is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Automation Systems at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the CRS1-RPT01 We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON CRS1-RPT01Automation Systems tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.
EE-SPX74 / SPX84 Slot-type Photomicrosensor with Connector (Modulated)/Features
E6F-C Incremental 60-mm-dia. Rotary Encoder/Features
S8VK-C Switch Mode Power Supply (60/120/240/480-W Models)/Features
K8DT-PH Phase-sequence Phase-loss Relay/Features
K8AK-PW Three-phase Voltage Relay/Features
Catalog Name | Catalog Number [size] | Last Update | |
---|---|---|---|
![]() | P056-E1-08 [4302KB] | May 07, 201820180507 | CompoNet Catalog |
last update: September 24, 2012
last update: September 24, 2012
last update: September 24, 2012
Name | Specifications | Model |
---|---|---|
Repeater Unit | A sub-trunk line can be connected downstream (for trunk-branch line configuration) or further branching is enabled downstream (for configurations with no wiring restrictions) in the same way as for a Master Unit. A Repeater Unit can be used to branch the trunk line and increase the number of connected Units, as well as to extend the length of the communications line. | CRS1-RPT01 * |
* These Units are also available with a DCN-TB4 Terminal Conversion Adapter included in the package. Add "(-B)" to
the end of the model number to receive the Adapter as well.
last update: September 24, 2012
last update: September 24, 2012
Item | Specification |
---|---|
Model | CRS1-RPT01 |
Communications ports | Upstream port (port 1): Ttrunk line or sub-trunk line Downstream port (port 2): Sub-trunk line (Can be wired with the same communications specifications as the Master Unit.) Different types of communications cable can be connected to the upstream and downstream ports. |
Maximum number of layers | Up to two extra segment layers can be created from the Master Unit. |
Number of nodes per network (per Master Unit) | 64 nodes |
Number of nodes per trunk line or sub-trunk line | 32 nodes (Including Slave Units) |
Communications power supply connector | One downstream communications port power supply connector Note: Communications power for the Repeater Unit is supplied from the BS+ and BS- terminals on the upstream port communications connector (PORT1). |
Communications power supply connector allowable current capacity | 5 A max. |
Noise immunity | Conforms to IEC 61000-4-4 2 kV (power line). |
Vibration resistance | 10 to 150 Hz with double-amplitude of 0.7 mm or 50 m/s2 |
Shock resistance | 150 m/s2 |
Dielectric strength | 500 VAC (between isolated circuits) |
Insulation resistance | 20 MΩ min. (between isolated circuits) |
Ambient operating temperature | -10 to 55°C |
Ambient operating humidity | 25% to 85% (with no condensation) |
Ambient operating atmosphere | No corrosive gases |
Storage temperature | -25 to 65°C |
Storage humidity | 25% to 85% (with no condensation) |
Installation | DIN Track or M4 screws |
Weight | 73 g |
Communications power supply voltage | 14 to 26.4 VDC |
Communications power supply current consumption | 95 mA max. |
last update: September 24, 2012