OMRON CRT1-TS04T / TS04P Automation Systems
last update: April 25, 2017
You can use either of two types of temperature input sensors: Thermocouple and resistance thermometer.
Each Unit provides four temperature inputs. Plus, the Units support scaling, comparators, and other data processing, reducing the processing load on the ladder program.
• Product lineup includes models with thermocouple inputs and models with resistance thermometer inputs.
• The node address, input types, and other settings can all be made using the switches on the Slave. (No Support Software is required.)
• Detachable terminal blocks enable easy maintenance without the need to remove wiring.
• Smart functions in the Slave reduce ladder programming and make maintenance easier.
For example, scaling to convert input data to desired values, comparators to compare process values with preset
upper and lower limits, and integrator to calculate the heat values of equipment or Sensors by from the temperature and
measurement time.
• The Sensor open-circuit detection function reduces wiring errors.
last update: April 25, 2017
If you have just landed here, this product OMRON CRT1-TS04T / TS04P Automation Systems,Automation Systems is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Automation Systems at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the CRT1-TS04T / TS04P We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON CRT1-TS04T / TS04PAutomation Systems tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.
X General-purpose Basic Switch/Features
MY Miniature Power Relays/Features
K3HB-V Weighing Indicator/Features
CS1W-PTS SYSMAC CS-series Process Analog I/O Units/Features
XW2C-20G6-IO16 Connector-Terminal Block Conversion Unit with Two-tiered I/O Terminal Block with C...
last update: October 17, 2012
| Name | Specifications | Model | ||
|---|---|---|---|---|
| Input/Output | Points | Specifications | ||
| Temperature Input Unit | Thermocouple Input | 4 inputs | Switchable between R, S, K, J, T, E, B, N, L, U, W, and PL2 | CRT1-TS04T |
| Platinum-resistance thermometer input | PT100 (-200 to 850°C) PT100 (-200 to 200°C) | CRT1-TS04P | ||
last update: October 17, 2012
last update: November 12, 2012
last update: November 12, 2012
last update: October 17, 2012
| Item | Specification |
|---|---|
| Communications power supply voltage | 14 to 26.4 VDC |
| I/O power supply voltage *1 | 20.4 to 26.4 VDC (24 VDC -15%/+10%) |
| Noise immunity | Conforms to IEC 61000-4-4, 2 kV (power line). |
| Vibration resistance | 10 to 60 Hz with double-amplitude of 0.7 mm, 60 to 150 Hz and 50 m/s2 in X, Y, and Z directions for 80 min each |
| Shock resistance | 150 m/s2 (3 times each in 6 directions on 3 axes) |
| Dielectric strength | 500 VAC (between isolated circuits) |
| Insulation resistance | 20 MΩ min. (between isolated circuits) |
| Ambient operating temperature | -10 to 55°C |
| Ambient operating humidity | 25% to 85% (with no condensation) |
| Ambient operating atmosphere | No corrosive gases |
| Storage temperature | -25 to 65°C |
| Storage humidity | 25% to 85% (with no condensation) |
| Terminal block screw tightening torque *2 | M3 wiring screws: 0.5 Nm M3 mounting screws: 0.5 Nm |
| Installation | Mounted on 35-mm DIN Track or Mounting Bracket, or secured with M4 screws (depending on model) |
*1 The I/O power supply is called the sensor power supply in information for the CRT1-VAD04S.
*2 Applicable only to Slaves to which screw terminal blocks are mounted.
| Model | CRT1-TS04T | CRT1-TS04P | |
|---|---|---|---|
| Input type | Switchable between R, S, K, J, T, E, B, N, L, U, W, and PL2 When set with CX-Integrator: Input types can be set individually for each input. Wen set with DIP switch: The same input type setting applies to all 4 inputs. | Switchable between PT100 (-200 to 850°C) and PT100 (-200 to 200°C) When set with CX-Integrator: Input types can be set individually for each input. When set with DIP switch: The same input type setting applies to all 4 inputs. | |
| Indicator accuracy | (±0.3% of indication value or ±1°C, whichever is larger) ±1 digit max. Indicator Accuracy in Exceptional Cases | -200 to 850°C input range: (±0.3% of indication value or ±0.8°C, whichever is larger) ±1 digit max. -200 to 200°C input range: (±0.3% of indication value or ±0.5°C, whichever is larger) ±1 digit max. | |
| Input type and temperature range | Input accuracy | ||
| K, T, and N below -100°C | ±2°C ±1 digit max. | ||
| U and L | ±2°C ±1 digit max. | ||
| R and S below 200°C | ±3°C ±1 digit max. | ||
| B below 400°C | Not specified. | ||
| W | ±0.3% of indication value or ±3°C (whichever is larger) ±1 digit max. | ||
| PL2 | ±0.3% of indication value or ±2°C (whichever is larger) ±1 digit max. | ||
| Conversion cycle | 250 ms/4 points | ||
| Temperature conversion data | Binary data (4-digit hexadecimal when Normal Display Mode is selected or 8-digit hexadecimal when 1/100 Display Mode is selected.) | ||
| Isolation method | Between input and communication lines: Photocoupler isolation Between temperature input signals: Photocoupler isolation | ||
| Mounting method | 35-mm DIN track mounting | ||
| Communications power supply current | 75 mA max. at 24 VDC 110 mA max. at 14 VDC | 75 mA max. at 24 VDC 110 mA max. at 14 VDC | |
| Weight | 148 g max. | 147 g max. | |
A cold junction compensator is included in the Terminal Block of the CRT1-TS04T. The input accuracy depends on the mounting direction if only the Unit is replaced.
| Mounting direction | Input accuracy | |
|---|---|---|
| Mounted normally | As specified in the Performance Specifications. | |
| Mounted in any direction other than the above | ±0.3% of indication value or ±2°C (whichever is larger) ±1 digit max. Indicator Accuracy in Exceptional Cases | |
| Input type and temperature range | Input accuracy | |
| K, T, and N below -100°C | ±3°C ±1 digit max. | |
| U and L | ±3°C ±1 digit max. | |
| R and S below 200°C | ±4°C ±1 digit max. | |
| B below 400°C | Not specified. | |
| W | ±0.3% of indication value or ±4°C (whichever is larger) ±1 digit max. | |
| PL2 | ±0.3% of indication value or ±3°C (whichever is larger) | |
last update: October 17, 2012
| Catalog Name | Catalog Number [size] | Last Update | |
|---|---|---|---|
| | P056-E1-08 [4302KB] | May 07, 201820180507 | CompoNet Catalog |