OMRON G70D-SOC16 / FOM16 Power Supplies / In Addition
last update: February 13, 2017
• Compact terminal is just 156 × 51 × 39 mm (W × D × H)
• Models with Power MOSFET Relays are available for high-frequency switching of AC or DC loads.
• Wire loads directly from terminals; no need for relaying.
• Operation indicators show each I/O signal’s ON/OFF status at a glance.
• The G70D-SOC16 and G70D-FOM16 can be combined with a DRT1-OD32ML I/O Terminal for DeviceNet connectivity or an SRT2-VOD16ML Connector Terminal for CompoBus/S connectivity.
• Equipped with surge-absorbing diodes.
• Relay Removal Tool included.
• Mount either to DIN rail or via screws.
last update: February 13, 2017
If you have just landed here, this product OMRON G70D-SOC16 / FOM16 Power Supplies / In Addition,Power Supplies / In Addition is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Power Supplies / In Addition at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the G70D-SOC16 / FOM16 We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON G70D-SOC16 / FOM16Power Supplies / In Addition tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.
V500-R2 Laser-type Bar Code Reader/Features
61F-G[]P Floatless Level Switch (Plug-in Type)/Features
G3NE Solid State Relays/Features
H5CX Digital Timer/Features
S8AS Smart Power Supply/Features
last update: February 13, 2017
Classification | Points | Internal I/O common | Rated voltage | Model |
---|---|---|---|---|
Relay outputs | 16 points (SPST-NO × 16) | NPN (+ common) | 24 V DC | G70D-SOC16 |
PNP (- common) | G70D-SOC16-1 | |||
Power MOSFET relay outputs | NPN (+ common) | G70D-FOM16 | ||
PNP (- common) | G70D-FOM16-1 |
Note: These are all non-standard model and require a special order. Contact your OMRON representative for details on
availability.
• Cable with Loose Wire and Crimp Terminals: XW2Z-RY[]C
• Cable with Loose Wires: XW2Z-RA[]C
• Cable with Fujitsu connectors (1:1): XW2Z-R[]C
(1:2): XW2Z-RI[]C-[]
XW2Z-RO[]C-[]
(1:3): XW2Z-R[]C-[]-[]
• Cable with MIL connectors (1:1): XW2Z-RI[]C
XW2Z-RO[]C
(1:2): XW2Z-RI[]-[]-D[]
XW2Z-RM[]-[]-D[]
XW2Z-RO[]-[]-D1
Refer to the XW2Z-R Datasheet (Cat. No. G126) for details.
Applicable Output Relay Terminals | Rated voltage | Model |
---|---|---|
G70D-SOC16 G70D-SOC16-1 | 24 V DC | G6D-1A-ASI DC24 |
G70D-FOM16 G70D-FOM16-1 | G3DZ-2R6PL DC24 * |
* This is a non-standard model and requires a special order.
Contact your OMRON representative for details on availability.
Refer to your OMRON website for details on the PFP-[].
last update: February 13, 2017
last update: April 3, 2017
The following specifications apply to G6D Relays mounted in a G70D Relay Terminal and not the G6D Relay itself.
Rated voltage | 24 V DC |
---|---|
Rated current | 10.5 mA |
Coil resistance | 2,880 Ω |
Must-operate voltage | 70% max. of rated voltage |
Must release voltage | 10% min. of rated voltage |
Max. voltage | 130% of rated voltage |
Power consumption | Approx. 200 mW |
Note: 1. The must-operate voltage is 75% or less of the rated voltage if the relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil temperature of 23° C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil temperature of 23° C.
4. The maximum allowable voltage is the maximum value of the allowable voltage range for the relay coil operating
power supply. There is no continuous allowance.
5. The rated current includes the terminal’s LED current.
Load | Resistive load (cosφ = 1) | |
---|---|---|
Rated load | 3 A at 250 V AC, 3 A at 30 V DC | |
Rated carry current | 3 A | |
Max. switching voltage | 250 V AC, 30 V DC | |
Max. switching current | 3 A | |
Min. permissible load (reference value) *2 | 10 mA at 5 V DC | |
Endurance | Electrical | 100,000 operations min. (under and at the rated load at 1,800 operations/hr) |
Mechanical | 20,000,000 operations min. (at 18,000 operations/hr) |
*1. Up to 3 A can be carried by the power supply terminals for outputs (terminals B0 to B7.)
*2. This value is for a switching frequency of 120 times per minute.
Note: The following specifications apply to G3DZ Power MOSFET relays mounted in a G70D Relay terminal and not the G3.
Rated voltage | 24 V DC | |
---|---|---|
Operating voltage | 19.2 to 28.8 V DC | |
Voltage level | Must-operate | 19.2 V DC max. |
Must release | 1 V DC min. | |
Input impedance | 4 kΩ±20% | |
Rated current | 8.2 mA±20% |
Note: The rated current includes the terminal’s LED current.
Load voltage | 3 to 264 V AC, 3 to 125 V DC |
---|---|
Load current | 100 μA to 0.3 A |
Inrush current | 6 A (10 ms) |
Item | G70D-SOC16(-1) | G70D-FOM16(-1) |
---|---|---|
Classification | Relay outputs | Power MOSFET relay outputs |
Contact configuration | 16 points (SPST-NO × 16) | |
Contact structure | Single | --- |
Contact material | Ag-Alloy (Cd free) | --- |
Contact resistance | 100 mΩ max. *1 | --- |
Must-operate time | 10 ms max. *2 | 6 ms max. |
Release time | 10 ms max. *2 | |
Isolation method | --- | Photocoupler |
Output ON-resistance | --- | 2.4 Ω max. |
Open-state leakage current | --- | 10 μA max. (at 125 V DC) |
Max. switching frequency | Mechanical: 18,000 operations/h Rated load: 1,800 operations/h | --- |
Insulation resistance | 100 MΩ min. (at 500 V DC) | |
Dielectric strength | 2,000 V AC for 1 min between coil and contact | 2,000 V AC for 1 min between input and output terminals |
Noise immunity | Power input (normal mode): 600 V for 10 min with a pulse width of 100 ns to 1 μs Power input (common mode): 1.5 kV for 10 min with a pulse width of 100 ns to 1 μs Input cable (coiling): 1.5 kV for 10 min with a pulse width of 100 ns to 1 μs Unit body (coiling): 600 V for 10 min with a pulse width of 100 ns to 1 μs | |
Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double) Malfunction: 10 to 55 to 10 Hz, 0.375-mm amplitude (0.75-mm double) | |
Shock resistance | Destruction: 300 m/s2 Malfunction: 100 m/s2 | |
Operating voltage range | 24 V DC +10%/-15% | |
Current consumption | Approx. 300 mA at 24 V DC *3 | Approx. 300 mA at 24 V DC *4 |
Cable length | Between block and controller: 5 m max. (reference value for AWG28) Between block and external device: Dependent on load | |
LED color | Operation indicator: orange; power supply: green | |
Coil surge absorber | Diode (400 V, 300 mA) | |
Ambient temperature | Operating: 0 to 55°C (with no icing or condensation) Storage: -20 to 65°C (with no icing or condensation) | |
Ambient humidity | Operating: 35% to 85% | |
Mounting strength | No damage when 49 N pull load was applied for 1 s in all directions (except for 9.8 N in direction of rail) | |
Terminal strength | Tightening torque: 0.78 to 0.98 N·m Pull strength: 49 N for 1 min | |
Weight | Approx. 200 g |
Note: These values are initial values.
*1. Measurement: 1 A at 5 V DC
*2. Ambient temperature: 23°C
*3. Current consumption is when all points are ON and includes G6D Relay coil current but does not include any external
load current.
*4. Current consumption is when all points are ON and includes G3DZ input current but does not include any external load
current.
last update: April 3, 2017
Catalog Name | Catalog Number [size] | Last Update | |
---|---|---|---|
![]() | - [1260KB] | Apr 03, 201720170403 | G70D-SOC16/FOM16 Data Sheet |
![]() | G126-E1-02 [2435KB] | Apr 03, 201720170403 | XW2Z-R Data Sheet |
![]() | J217-E1-02 [1206KB] | Jun 01, 201820180601 | G70[]/G7TC Table of I/O Relay Terminal and connectable device combinations |
last update: February 13, 2017