OMRON 61F-G[]P Switches
last update: December 19, 2013
• Large switching capacity: 5 A at 220 VAC (resistive load).
• Easy to handle with DIN rail mounting.
• Replace for maintenance without rewiring the socket.
last update: December 19, 2013
If you have just landed here, this product OMRON 61F-G[]P Switches,Switches is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Switches at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the 61F-G[]P We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON 61F-G[]PSwitches tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.
G9SA Safety Relay Unit/Features
E5AR-T Programmable Digital Controller/Features
H3DK-M / -S Multi-range, Multi-mode Timer/Features
GT1-TS04[] Temperature Input Units/Features
K8AK-VW Single-phase Overvoltage/Undervoltage Relay/Features
last update: April 2, 2018
Type | General-purpose | Long-distance (for 2 km) | Long-distance (for 4 km) |
---|---|---|---|
Model | Model | Model | |
G1 models | 61F-G1P * | 61F-G1PL 2K | 61F-G1PL 4KM * |
Type | High-sensitivity | Low-sensitivity |
---|---|---|
Model | Model | |
G1 models | 61F-G1PH * | 61F-G1PD * |
Type | General-purpose | Long-distance (for 2 km) | Long-distance (for 4 km) |
---|---|---|---|
Model | Model | Model | |
G2 models | 61F-G2P * | 61F-G2PL 2KM * | 61F-G2PL 4KM * |
Type | High-sensitivity | Low-sensitivity |
---|---|---|
Model | Model | |
G2 models | 61F-G2PH * | 61F-G2PD * |
Type | General-purpose | Long-distance (for 2 km) | Long-distance (for 4 km) |
---|---|---|---|
Model | Model | Model | |
I models | 61F-IP * | 61F-IPL 2KM * | 61F-IPL 4KM * |
Type | High-sensitivity | Low-sensitivity |
---|---|---|
Model | Model | |
I models | 61F-IPH * | 61F-IPD * |
Note: When ordering, specify the desired operating voltage at the end of the model number.
* 61F-G[]P[] (110 VAC) in this catalog have been discontinued at the end of March 2018.
last update: April 2, 2018
last update: April 2, 2018
Item | General-purpose Controller 61F-G1P 61F-G2P 61F-IP | Long-distance Controllers 61F-G1PL 61F-G2PL 61F-IPL *2 | High-sensitivity Controllers 61F-G1PH 61F-G2PH 61F-IPH *1, *6 | Low-sensitivity Controller 61F-G1PD 61F-G2PD 61F-IPD |
---|---|---|---|---|
Controlling materials and operating conditions | For control of ordinary purified water or sewage water | For control of ordinary purified water in cases where the distance between sewage pumps and water tanks or between receiver tanks and supply tanks is long or where remote control is required. | For control of liquids with high specific resistance such as distilled water | For control of liquids with low specific resistance such as salt water, sewage water, acid chemicals, alkali chemicals |
Supply voltage | 100, 200, 220 VAC; 50/60 Hz | |||
Operating voltage range | 85% to 110% of rated voltage | |||
Interelectrode voltage | 8 VAC | 24 VAC | 8 VAC | |
Interelectrode current | Approx. 1 mA AC max. | Approx. 0.4 mA AC max. | Approx. 1.2 mA AC max. | |
Power consumption | Approx. 6.4 VA max. | |||
Interelectrode operate resistance | 0 to approx. 4 kΩ | 0 to 1.8 kΩ (for 2 km) 0 to 0.7 kΩ (for 4 km) | Approx. 15 kΩ to approx. 70 kΩ *5 | 0 to approx. 1.8 kΩ |
Interelectrode release resistance | Approx. 15 k to ∞ Ω | 4 k to ∞ Ω (for 2 km) 2.5 k to ∞ Ω (for 4 km) | Approx. 300 k to ∞ Ω | Approx. 5 k to ∞ Ω |
Response time | Operate: 80 ms max. Release: 160 ms max. | |||
Cable length *3 | 1 km max. | 2 km max. 4 km max. | 50 m max. | 1 km max. |
Control output | 2 A, 200 VAC (Inductive load: cosφ = 0.4) 5 A, 200 VAC (Resistive load) | |||
Ambient temperature | Operating: -10 to 55°C | |||
Ambient humidity | Operating: 45% to 85% RH | |||
Insulation resistance *4 | 100 MΩ min. (at 500 VDC) | |||
Dielectric strength *4 | 2000 VAC, 50/60 Hz for 1 min. | |||
Life expectancy | Electrical: 500,000 operations min. Mechanical: 5,000,000 operations min. | |||
Weight | Approx. 495 g |
*1. The relay in the 61F-G1H/-G2H/-IPH de-energizes when there is water present across the Electrodes, whereas the
relay in the 61F-GP-N8HY energizes when there is water present across the Electrodes.
*2. Models are available for 2 km and 4 km.
*3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will
become shorter as the cable diameter or number of conductors becomes larger. For details, refer to Safety
Precautions for Floatless Level Controllers.
*4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals,
between power terminals and contact terminals, and between Electrode terminals and contact terminals. For details,
refer to Safety Precautions for Floatless Level Controllers.
*5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
*6. High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation
electrodes), the internal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation
electrodes), the internal relay will operate.
last update: April 2, 2018
Catalog Name | Catalog Number [size] | Last Update | |
---|---|---|---|
![]() | - [901KB] | Apr 02, 201820180402 | 61F-G[]P Data Sheet |
![]() | N217-E1-01 [2428KB] | Jun 12, 201720170612 | Device Selection Guide for Water Level Control Applications |
last update: September 24, 2012
last update: September 24, 2012