OMRON CJ1W-PRM21 Automation Systems
last update: February 7, 2014
• PROFIBUS-DP master class one with support of DP-V1 data types.
• 7 kWord I/O
• Simple configuration through FDT/DTM based configurator
• Special CPU unit
• Handles data independent of the CPU unit, thus reducing CPU load
last update: February 7, 2014
If you have just landed here, this product OMRON CJ1W-PRM21 Automation Systems,Automation Systems is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Automation Systems at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the CJ1W-PRM21 We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON CJ1W-PRM21Automation Systems tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.
R88M-K, R88D-KN[]-ML2 G5-series AC Servomotors/Servo Drives with Built-in MECHATROLINK-II Communi...
CX-Designer FA Integrated Tool Package CX-One/Features
DZ Special-purpose Basic Switch/Features
G9B Stepping Relay Unit/Features
Viper 850 Articulated Robots/Features
last update: February 07, 2014
No information is available
last update: February 07, 2014
last update: February 07, 2014
Name | Specifications | Model |
---|---|---|
PROFIBUS-DP Master Unit | Controls up to 7000 words of remote I/O data over PROFIBUS-DP | CJ1W-PRM21 |
last update: February 07, 2014
Catalog Name | Catalog Number [size] | Last Update | |
---|---|---|---|
![]() | P04E-EN-03A [14041KB] | Jul 11, 200620060711 | Modular PLC series Catalog |
last update: February 07, 2014
Model | Remarks | ||
---|---|---|---|
CJ1W- PRM21 | Main function | Basic PROFIBUS-DP master Class 1 functions plus: DPV1 data types support | |
Unit No. | 0-15 | Special CPU unit | |
Maximum number of units mountable per PLC | 16 | Maximum depends on PLC CPU-type | |
Configurator | CX-PROFIBUS, FTD/DTM based configurator | Incorporates a Generic DTM to use with GSD-file based slaves | |
Supported baud rate(s) | All baud rates as specified by the standard EN50170 Volume 2, the PROFIBUS extensions to EN50170, as well as the standard IEC61158: 9.6 kBit/s, 19.2 kBit/s, 45.45 kBit/s. 93.75 kBit/s, 187.5 kBit/s, 500 kBit/s, 1.5 MBit/s, 3 MBit/s, 6 MBit/s, 12 MBit/s | The baud rate value to be used must be selected through the Configurator. | |
Selectable PROFIBUS address | 0-125 | Set through the configurator | |
Maximum number of PROFIBUS slaves | 125 | ||
Maximum number of I/O points | 7168 words | ||
Maximum number of I/O points per PROFIBUS slave | 244 bytes In / 244 bytes Out | ||
Control and status ares size | 25 words | ||
Supported Global_Control services | - Sync - Unsync - Freeze - Unfreeze - Clear | Through Control Area | |
Supported Master-Slave communication services | - Data_Exchange - Slave_Diag - Set_PRM - Chk_Cfg - Global_Control | ||
Power consumption | 400 mA at 5 V | ||
Dimensions | 90 x 65 x 31 mm | ||
Weight | 100 gr | ||
Ambient temperature | Operating: 0 °C to 50 °C |