OMRON H3AM Control Components
last update: December 19, 2013
• Incorporating an easy-to-see large setting dial with moving pointers.
• Wide time-setting range of 0.2 s to 60 h (available through three time-range model types)
• Wide AC power supply range (100 to 240 VAC)
• IP65 watertight and dust-tight front panel.
• Approved by UL and CSA.
• Conforms to EN61812-1 and IEC60664-1 4 kV for Low Voltage, and EMC Directives.
• Conforms to EMC standards.
• Six-language instruction manual provided.
• Programmable contact enables the building of a self-holding relay circuit as well as built-in instantaneous contact. (-NS)
• Memory retention (-NSR)
• Finger protection terminal block
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
last update: December 19, 2013
If you have just landed here, this product OMRON H3AM Control Components,Control Components is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Control Components at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the H3AM We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON H3AMControl Components tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.
E4C-UDA Digital Amplifier Ultrasonic Sensor/Features
NYP Industrial PC Platform NY-series Industrial Panel PC/Features
E2EZ Chip-immune Inductive Proximity Sensor/Features
NL Limit Touch Switch/Features
CK3W-PD048 CK3W Power Supply Unit/Features
last update: June 10, 2014
Operating mode | ON-delay |
---|---|
Screw tightening torque | 0.98 Nm (10 kgf) max. |
Input type | Voltage input |
Output type | Relay: DPDT |
Mounting method | Flush/Panel mounting, no restriction on mounting angle. |
Approved standards | UL 508, CSA C22.2 No. 14 Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1 |
Model | Full scale on dial | Set time unit | |||||
---|---|---|---|---|---|---|---|
s | 10 s | min | 10 min | h (hour) | 10 h (hour) | ||
H3AM-[][][]-A | 3 | --- | 0.5 to 30 s | 0.05 to 3 min | 0.5 to 30 min | 0.05 to 3 h | 0.5 to 30 h |
H3AM-[][][]-B | 6 | --- | 1 to 60 s | 0.1 to 6 min | 1 to 60 min | 0.1 to 6 h | 1 to 60 h |
H3AM-[][][]-C | 12 | 0.2 to12 s | 2 to 120 s | 0.2 to 12 min | 2 to 120 min | 0.2 to 12 h | --- |
Note: Instantaneous output is obtained by turning the time setting knob below "0" until the time setting knob stops.
Rated supply voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 85% to 110% of rated supply voltage |
Power reset (-NS) | Minimum power-opening time: 0.5 s |
Reset input time (-NSR) | Minimum input time: 0.5 s |
Reset voltage range (-NSR) | H level: 85 to 264 VAC L level: 0 to 10 VAC |
Power consumption | Approx. 9 VA (Approx. 5 W) |
Control output | Relays in H3AM-NS (R1) (R2) Relay in H3AM-NS (R2) (Contact material: AgSnIn) Contact output: 5 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load: 10 mA at 5 VDC (failure level: P, reference value) Relay in H3AM-NSR (R1) (Contact material: AgSnIn) Contact output: 5 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load: 100 mA at 5 VDC (failure level: P, reference value) |
Ambient temperature | Operating: -10°C to 55°C (with no icing) Storage: -25°C to 65°C (with no icing) |
Ambient humidity | Operating: 35% to 85% |
Accuracy of operating time | ±0.7% FS max. |
---|---|
Setting error | ±2% FS max. |
Reset time | Power reset: 0.5 s max. Reset input time: 0.5 s max. |
Influence of voltage | ±1% FS max. |
Influence of temperature | ±2% FS max. |
Insulation resistance | 100 MΩ max. (at 500 VDC) |
Dielectric strength | 2,000 VAC (50/60 Hz) for 1 min between exposed non-current-carrying metal parts and current-carrying metal parts 2,000 VAC (50/60 Hz) for 1 min between the operating circuit and control output terminals 1,000 VAC (50/60 Hz) for 1 min between the operating power supply circuit and reset input circuit (H3AM-NSR only) 1,000 VAC (50/60 Hz) for 1 min between contacts not located next to each other 2,000 VAC (50/60 Hz) for 1 min between contacts of opposite poles |
Impulse withstand voltage | 5 kV between power terminals 5 kV between exposed non-current-carrying metal parts and current-carrying metal parts |
Noise immunity | ±1.5 kV (between power terminals) square-wave noise by a noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) |
Static immunity | Malfunction: 8 kV Destruction: 15 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 2 cycles each in 3 directions (8 min per cycle) Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 2 cycles each in 3 directions (8 min per cycle) |
Shock resistance | Destruction: 300 m/s2 3 times each in 6 directions Malfunction: 150 m/s2 (100 m/s2 in the front/back direction) 3 times each in 6 directions |
Life expectancy | Mechanical: 5,000,000 times min. (under no load at 1,800 times/h) Electrical: 100,000 times min. (5-A at 250 VAC, resistive load at 1,800 times/h) |
Motor life expectancy | 20,000 h |
EMC | (EMI): EN61812-1 Emission Enclosure: EN55011 class A Emission AC Mains: EN55011 class A (EMS): EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Power Frequency Magnetic Fields: IEC61000-4-8 Immunity Voltage Dip/Interruption: IEC61000-4-11 |
Enclosure rating | IP65 (front panel only) * IP20 (terminal section) |
Weight | Approx. 350 g |
* A separately sold waterproof packing (Y92S-35) is necessary to ensure IP65 waterproofing between the Timer and
installation panel.
The H3AM-NS[]-[]-300 model with waterproof packing is available.
last update: June 10, 2014
Catalog Name | Catalog Number [size] | Last Update | |
---|---|---|---|
![]() | - [762KB] | Jun 09, 201420140609 | H3AM Data Sheet |
![]() | - [43KB] | Mar 12, 201820180312 | Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance |
last update: September 24, 2012
Note:Tightening torque for panel mounting is as follows: 0.3 Nm ±0.05 Nm
last update: September 24, 2012
last update: September 24, 2012
Rated supply voltage | Resetting system (See note.) | Control output | Time range | ||
---|---|---|---|---|---|
0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h) | 1 s to 60 h (60 s, 6 min, 60 min, 6 h, 60 h) | 0.2 s to 12 h (12 s, 120 s, 12 min, 120 min, 12 h) | |||
100 to 240 VAC | Self-resetting | DPDT contact output (Time-limit output SPDT and switchable SPDT (time-limit ↔ instantaneous)) | H3AM-NS-A | H3AM-NS-B | H3AM-NS-C |
Electric resetting | DPDT contact output (Time-limit output SPDT and instantaneous output SPDT) | H3AM-NSR-A | H3AM-NSR-B | H3AM-NSR-C |
Note:Note: The operation of the instantaneous contacts differs for the self-resetting and electric resetting systems.
Item | Model |
---|---|
Waterproof Packing | Y92S-35 (See note.) |
Note:Note: Supplied with H3AM-NS[]-[]-300 models.