OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 Digital I/O Terminal 3-tier Terminal Block Type/Features Networks--OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 Online Store

OMRON GX-ID16[]2 / OD16[]2 / MD16[]2Automation Systems/ Networks/EtherCAT

OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 Automation Systems

OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 Dimensions

/Images/l_2955-25-118903-198x198.jpg

• It is unnecessary to share the common terminal among multiple contacts.
  Easy-to-find wiring locations.

• Detachable screw terminal block facilitates the maintenance.

• Input response time can be switched for high-speed processing.

• Selectable node address setting methods: setting with rotary switch and with tool software.
  When setting the nodes with rotary switch, setting is easy and node identification becomes possible for maintenance.

Purchase the OMRON EtherCAT Please fill in the following

Title:

Email:

Tel:

Content:

Verification code:

If you have just landed here, this product OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 Automation Systems,Automation Systems is offered online by Tianin FLD Technical Co.,Ltd. This is an online store providing Automation Systems at wholesale prices for consumers. You can call us or send enquiry, we would give you the prices, packing,deliverty and more detailed information on the GX-ID16[]2 / OD16[]2 / MD16[]2 We cooperate with DHL,TNT,FEDEX,UPS,EMS,etc.They guarantee to meet your needs in terms of time and money,even if you need your OMRON GX-ID16[]2 / OD16[]2 / MD16[]2Automation Systems tomorrow morning (aka overnight or next day air) on your desk, 2, 3 days or more.Note to international customers, YES, we ship worldwide.

NYB Industrial PC Platform NY-series Industrial Box PC/Features
FJ Series (Camera and Software Vision Package) PC Vision System/Features
G7T I/O Relay/Features
G3PE (Single-phase) Solid State Relays for Heaters/Features
K3HB-X Process Indicator/Features


OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 specification

GX-ID16[]2 / OD16[]2 / MD16[]2 Digital I/O Terminal 3-tier Terminal Block Type/Specifications

General Specifications

ItemSpecification
Unit power supply voltage20.4 to 26.4 VDC (24 VDC -15% to +10%)
I/O power supply voltage20.4 to 26.4 VDC (24 VDC -15% to +10%)
Noise resistanceConforms to IEC 61000-4-4, 2 kV (power line)
Vibration resistanceMalfunction 10 to 60 Hz with amplitude of 0.7 mm, 60 to 150Hz and 50 m/s2 in X, Y,
and Z directions for 80 minutes
<Relay Output Unit GX-OC1601 only>
10 to 55 Hz with double-amplitude of 0.7 mm
Impact resistance150 m/s2 with amplitude of 0.7 mm
<Relay Output Unit GX-OC1601 only>
100 m/s2 (3 times each in 6 directions on 3 axes)
Dielectric strength600 VAC (between isolated circuits)
Isolation resistance20 MΩ or more (between isolated circuits)
Ambient operating temperature-10 to 55 °C
Operating humidity25% to 85% (with no condensation)
Operating atmosphereNo corrosive gases
Storage temperature-25 to 65 °C
Storage humidity25% to 85% (with no condensation)
Terminal block screws
tightening torque *
M3 wiring screws: 0.5 Nm
M3 terminal block mounting screws: 0.5 Nm
Mounting method35-mm DIN track mounting
* Applicable only to 2-tier terminal block and 3-tier terminal block type slaves.

Input Section Specifications

16-point Input Terminals

ItemSpecification
GX-ID1612GX-ID1622
Input capacity16 points
Internal I/O commonNPNPNP
ON voltage15 VDC min. (between each input terminal
and the V terminal)
15 VDC min. (between each input terminal
and the G terminal)
OFF voltage5 VDC max. (between each input terminal
and the V terminal)
5 VDC max. (between each input terminal
and the G terminal)
OFF current1.0 mA max.
Input current6.0 mA max./input (at 24-VDC)
3.0 mA min./input (at 17-VDC)
ON delay0.1 ms max.
OFF delay0.2 ms max.
Input filter valueWithout filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms)
Number of circuits per
common
8 points/common
Input indicatorsLED display (yellow)
Isolation methodPhotocoupler isolation
I/O power supply methodSupply by I/O power supply
Input device supply current100 mA/point
Unit power supply current
consumption
90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current
consumption
5 mA max. (for 20.4 to 26.4-VDC power supply voltage)
Weight370 g max.
Expansion functionsNo
Short-circuit protection
function
No
Note: For the I/O power supply current value to V and G terminals, refer to GX Series Operation Manual (Cat. No. W488).

Output Section Specifications

16-point Output Terminals

ItemSpecification
GX-OD1612GX-OD1622
Output capacity16 points
Rated current (ON current)0.5 A/output, 4.0 A/common
Internal I/O commonNPNPNP
Residual voltage1.2 V max. (0.5 ADC, between each
output terminal and the G terminal)
1.2 V max. (0.5 ADC, between each
output terminal and the V terminal)
Leakage current0.1 mA max.
ON delay0.5 ms max.
OFF delay1.5 ms max.
Number of circuits per common8 points/common
Output indicatorsLED display (yellow)
Isolation methodPhotocoupler isolation
I/O power supply methodSupply by I/O power supply
Output device supply current100 mA/point
Unit power supply current consumption90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption5 mA max. (for 20.4 to 26.4-VDC power supply voltage)
Weight370 g max.
Expansion functionsNo
Output handling for communications errorsSelect either hold or clear
Short-circuit protection functionNo
Note: For the I/O power supply current value to V and G terminals, refer to GX Series Operation Manual (Cat. No. W488).

Input and Output Section Specifications

8-point Input and 8-point output Terminals

General Specifications

ItemSpecification
GX-MD1612GX-MD1622
Internal I/O commonNPNPNP
I/O indicatorsLED display (yellow)
Unit power supply current consumption90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
Weight370 g max.
Expansion functionsNo
Short-circuit protection functionNo

Input Section

ItemSpecification
GX-MD1612GX-MD1622
Input capacity8 points
ON voltage15 VDC min. (between each input terminal
and the V terminal)
15 VDC min. (between each input terminal
and the G terminal)
OFF voltage5 VDC max. (between each input terminal
and the V terminal)
5 VDC max. (between each input terminal
and the G terminal)
OFF current1.0 mA max./input
Input current6.0 mA max./input (at 24-VDC)
3.0 mA min./input (at 17-VDC)
ON delay0.1 ms max.
OFF delay0.2 ms max.
Input filter valueWithout filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms)
Number of circuits per
common
8 points/common
Isolation methodPhotocoupler isolation
I/O power supply methodSupply by I/O power supply
Input device supply current100 mA/point
I/O power supply current
consumption
5 mA max. (for 20.4 to 26.4-VDC power supply voltage)

Output Section

ItemSpecification
GX-MD1612GX-MD1622
Output capacity8 points
Rated output current0.5 A/output, 2.0 A/common
Residual voltage1.2 V max. (0.5 ADC, between each
output terminal and the G terminal)
1.2 V max. (0.5 ADC, between each
output terminal and the V terminal)
Leakage current0.1 mA max.
ON delay0.5 ms max.
OFF delay1.5 ms max.
Number of circuits per common8 points/common
Isolation methodPhotocoupler isolation
I/O power supply methodSupply by I/O power supply
Output device supply current100 mA/point
I/O power supply current consumption5 mA max. (for 20.4 to 26.4-VDC power supply voltage)
Output handling for communications errorsSelect either hold or clear
Note: For the I/O power supply current value to V and G terminals, refer to GX-Series Operation Manual (Cat. No. W488).


OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 catalog

GX-ID16[]2 / OD16[]2 / MD16[]2 Digital I/O Terminal 3-tier Terminal Block Type/Catalog

  • Catalog
  • Manual
  • CAD

English

Global Edition

For ordering in Singapore, please note some product models not sold in Singapore may be included in the following catalog(s) for our global customers.

*It is recommended to select “Save” from the right-click due to large size of catalog PDF data.

Catalog Name Catalog Number
[size]
Last Update
GX Series Data Sheet -
[5900KB]
Jan 17, 201920190117 GX Series Data Sheet


OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 lineup

GX-ID16[]2 / OD16[]2 / MD16[]2 Digital I/O Terminal 3-tier Terminal Block Type/Lineup

International Standards

• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA,
   UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EU
   Directives, RCM: RCM mark, and KC: KC Registration.
• Contact your OMRON representative for further details and applicable conditions for these standards.

NameSpecificationsModelStandards
3-tier terminal blocksInputs16 inputsNPNGX-ID1612CE
PNPGX-ID1622CE
Outputs16 outputsNPNGX-OD1612CE
PNPGX-OD1622CE
Inputs/Outputs8 inputs/8 outputsNPNGX-MD1612CE
PNPGX-MD1622CE


OMRON GX-ID16[]2 / OD16[]2 / MD16[]2 dimension

GX-ID16[]2 / OD16[]2 / MD16[]2 Digital I/O Terminal 3-tier Terminal Block Type/Dimensions

GX-ID1612/ID1622
GX-OD1612/OD1622
GX-MD1612/MD1622

GX-ID16[]2 / OD16[]2 / MD16[]2 Dimensions 1


Return to OMRON